Description
Specifications
Main | |
Range | Acti9 |
range of product | Acti9 iEM3000 |
Product or component type | Energy meter |
Device short name | iEM3350 |
Market segment | Buildings small building cost management: billing: main incomer Buildings small building cost management: billing: sub feeder Buildings small building cost management: billing: panelboard Buildings medium building cost management: billing: main incomer Buildings medium building cost management: billing: sub feeder Buildings medium building cost management: billing: panelboard Buildings large building cost management: billing: main incomer Buildings large building cost management: billing: sub feeder Buildings large building cost management: billing: panelboard Buildings multi-site cost management: billing: main incomer Buildings multi-site cost management: billing: sub feeder Buildings multi-site cost management: billing: panelboard Data center cost management: billing Healthcare cost management: billing Industry cost management: billing Buildings small building cost management: cost allocation: main incomer Buildings small building cost management: cost allocation: sub feeder Buildings small building cost management: cost allocation: panelboard Buildings medium building cost management: cost allocation: main incomer Buildings medium building cost management: cost allocation: sub feeder Buildings medium building cost management: cost allocation: panelboard Buildings large building cost management: cost allocation: main incomer Buildings large building cost management: cost allocation: sub feeder Buildings large building cost management: cost allocation: panelboard Buildings multi-site cost management: cost allocation: main incomer Buildings multi-site cost management: cost allocation: sub feeder Buildings multi-site cost management: cost allocation: panelboard Data center cost management: cost allocation Healthcare cost management: cost allocation Industry cost management: cost allocation |
Complementary | |
Poles description | 3P + N 3P 1P + N |
Type of measurement | Active energy Current Voltage Active power |
Device application | Partial meter Sub billing |
Accuracy class | Class 1 active energy conforming to IEC 62053-21 Class 1 active energy conforming to IEC 61557-12 Class B active energy conforming to EN 50470-3 |
input type | Direct connection |
[In] rated current | 125 A |
Rated voltage | 100…277 V 173…480 V |
Network frequency | 50 Hz 60 Hz |
Technology type | Electronic |
Display type | LCD display |
Sampling rate | 32 samples/cycle |
Measurement current | 0…125 A |
Maximum value measured | 99999999.9 kWh |
Communication port protocol | Modbus RTU at 9.6, 19.2 and 38.4 kbauds even/odd or none, insulation 4000 V |
Communication port support | Screw terminal block: RS485 |
Local signalling | Green indicator light: power ON Yellow flashing LED: accuracy checking Yellow indicator light: communications are active on the Modbus port (Modbus) |
Number of inputs | 0 |
Number of outputs | 0 |
Mounting mode | Clip-on |
Mounting support | DIN rail |
Connections – terminals | Screw terminals 50 mm² cable(s) |
Overvoltage category | III |
Standards | BS EN 61557-12:2021 IEC 61557-12:2021 EN 61557-12:2021 BS EN 61326-1 IEC 61326-1 EN 61326-1 BS EN 62052-11:2020 IEC 62052-11:2020 EN 62052-11:2020 BS EN 62053-21 IEC 62053-21 EN 62053-21 BS EN 62052-31:2015 IEC 62052-31:2015 EN 62052-31:2015 BS EN 61010-1:2010 EN 61010-1:2010 IEC 61010-1:2010 UL 61010-1:2010 BS EN 61010-2-30 IEC 61010-2-30 EN 61010-2-30 UL 61010-2-30 ANSI C12.16 |
Product certifications | CE conforming to IEC 61010-1 (safety) CE conforming to EN 61557-12 (power monitor) CE conforming to EN/IEC 61326-1 (EMC) UKCA conforming to BS EN 61010-1 (safety) UKCA conforming to BS EN 61557-12 (power monitor) UKCA conforming to BS EN 61326-1 (EMC) CULus conforming to UL 61010-1 (safety) CULus conforming to EN 61010-1 (safety) EAC (sub-meter) KZ conforming to NMI M 6-1 KZ NMI conforming to NMI M 6-1 |
Compatibility code | IEM3350 |
Environment | |
IP degree of protection | IP40 front panel: conforming to IEC 60529 IP20 body: conforming to IEC 60529 |
pollution degree | 2 |
Relative humidity | 5…95 % at 50 °C |
Ambient air temperature for operation | -25…70 °C – IEC |
Ambient air temperature for storage | -40…85 °C |
Operating altitude | < 3000 m |
Colour | White |
9 mm pitches | 14 |
Width | 126 mm |
Height | 103.2 mm |
Depth | 69.3 mm |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 8.000 cm |
Package 1 Width | 11.000 cm |
Package 1 Length | 13.000 cm |
Package 1 Weight | 692.000 g |
Unit Type of Package 2 | S03 |
Number of Units in Package 2 | 18 |
Package 2 Height | 30.000 cm |
Package 2 Width | 30.000 cm |
Package 2 Length | 40.000 cm |
Package 2 Weight | 12.700 kg |
Reviews