Main | |
Range | Domae |
Product or component type | Residual current circuit breaker (RCCB) |
Device short name | RCCB |
Device application | Protection |
Poles description | 4P |
Earth-leakage protection class | Type AC |
Suitability for isolation | Yes |
Complementary | |
Neutral position | Left |
[In] rated current | 63 A |
Network type | AC |
Network frequency | 50 Hz |
[Ue] rated operational voltage | 400 V AC 50 Hz |
Earth-leakage sensitivity | 30 mA |
Earth-leakage protection time delay | Instantaneous |
Rated breaking and making capacity | 3000 A |
Rated conditional short-circuit current | Fuse: 6000 A |
[Ui] rated insulation voltage | 440 V AC 50 Hz |
[Uimp] rated impulse withstand voltage | 4 kV |
Surge current | 250 A |
control type | Toggle |
local signalling | ON/OFF indication |
Mounting mode | Clip-on |
Mounting support | DIN rail |
Comb busbar and distribution block compatibility | YES |
Connection pitch | 18 mm |
9 mm pitches | 8 |
Height | 81 mm |
Width | 72 mm |
Depth | 76 mm |
Embedding depth | 44 mm |
Net weight | 350 kg |
Colour | White |
Mechanical durability | 5000 cycles |
Electrical durability | 2000 cycles |
Connections – terminals | Tunnel type terminals (top or bottom) 1…35 mm² rigid Tunnel type terminals (top or bottom) 1…25 mm² flexible |
Wire stripping length | 14 mm |
Tightening torque | 3.5 N.m |
Environment | |
Standards | IEC 61008-1 |
Product certifications | SNI |
IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
Pollution degree | 2 |
Overvoltage category | III |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
ambient air temperature for operation | -5…40 °C |
Ambient air temperature for storage | -40…60 °C |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 8.0 cm |
Package 1 Width | 7.2 cm |
Package 1 Length | 8.5 cm |
Package 1 Weight | 340.0 g |