Description
Specifications
Main | |
Range | Easy TeSys |
Range of product | Easy TeSys Control Relay |
Product or component type | Control relay |
Device short name | CAE |
Contactor application | Control circuit |
Colour | Grey (RAL 7011) |
Complementary | |
Utilisation category | AC-14 AC-15 |
Pole contact composition | 3 NO + 1 NC |
[Ue] rated operational voltage | <= 690 V AC |
Control circuit type | AC at 50 Hz |
[Uc] control circuit voltage | 220 V AC 50 Hz |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
[Ith] conventional free air thermal current | 10 A (at 40 ยฐC) |
Irms rated making capacity | 140 A at 690 V AC conforming to IEC 60947-5-1 |
[Icw] rated short-time withstand current | 120 A – 500 ms 140 A – 100 ms |
Associated fuse rating | 10 A gG at 690 V conforming to IEC 60947-5-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1 |
Mounting support | Plate Rail |
Connections – terminals | Screw clamp terminals 1 1โฆ2.5 mmยฒ – cable stiffness: flexible without cable end Screw clamp terminals 2 1โฆ2.5 mmยฒ – cable stiffness: flexible without cable end Screw clamp terminals 1 1โฆ2.5 mmยฒ – cable stiffness: flexible with cable end Screw clamp terminals 2 1โฆ2.5 mmยฒ – cable stiffness: flexible with cable end Screw clamp terminals 1 1โฆ2.5 mmยฒ – cable stiffness: solid without cable end Screw clamp terminals 2 1โฆ2.5 mmยฒ – cable stiffness: solid without cable end |
Recommended tightening torque | 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2 |
Control circuit voltage limits | Operational: 0.85…1.1 Uc at 50 Hz Drop-out: 0.3…0.6 Uc |
Operating time | 4…19 ms coil energisation and NC opening 12…22 ms coil energisation and NO closing 4…12 ms coil de-energisation and NC opening 6…17 ms coil de-energisation and NO closing |
Mechanical durability | 10 Mcycles |
Maximum operating rate | 180 cyc/mn |
Inrush power in VA | 70 VA 50 Hz (at 20 ยฐC) |
Hold-in power consumption in VA | 8 VA 50 Hz (at 20 ยฐC) |
Minimum switching voltage | 17 V |
Minimum switching current | 5 mA |
Non-overlap time | 1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact |
Insulation resistance | > 10 MOhm |
Mechanical robustness | Shocks control relay open: 7 Gn for 11 ms Shocks control relay closed: 10 Gn for 11 ms Vibrations control relay open: 1.5 Gn, 5…300 Hz Vibrations control relay closed: 3 Gn, 5…300 Hz |
Height | 74 mm |
Width | 45 mm |
Depth | 80 mm |
Net weight | 0.28 kg |
Environment | |
Standards | IEC 60947-5-1 |
Product certifications | GOST |
IP degree of protection | IP2X conforming to IEC 60529 |
Protective treatment | TH conforming to IEC 60068 |
Ambient air temperature for operation | -20โฆ70 ยฐC |
Ambient air temperature for storage | -60โฆ80 ยฐC |
Operating altitude | 3000 m without derating |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 5.000 cm |
Package 1 Width | 7.500 cm |
Package 1 Length | 8.500 cm |
Package 1 Weight | 293.000 g |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 36 |
Package 2 Height | 15.000 cm |
Package 2 Width | 30.000 cm |
Package 2 Length | 40.000 cm |
Package 2 Weight | 10.842 kg |
Unit Type of Package 3 | P06 |
Number of Units in Package 3 | 576 |
Package 3 Height | 75.000 cm |
Package 3 Width | 60.000 cm |
Package 3 Length | 80.000 cm |
Package 3 Weight | 181.472 kg |
Contractual warranty | |
Warranty | 18 months |
Reviews