Description
Specifications
Main | |
Range of product | Altivar Process ATV600 |
Product specific application | Process and utilities |
Product or component type | Variable speed drive |
Variant | Standard version |
Device short name | ATV630 |
Mounting mode | Wall mount |
Communication port protocol | Ethernet Modbus serial Modbus TCP |
[Us] rated supply voltage | 380…480 V – 15…10 % |
[Us] rated supply voltage | 380…480 V |
Relative symmetric mains voltage tolerance | 10 % |
Relative symmetric network frequency tolerance | 5 % |
nominal output current | 173.0 A |
IP degree of protection | IP21 |
Product destination | Asynchronous motors Synchronous motors |
EMC filter | Integrated with 150 m conforming to IEC 61800-3 category C3 |
IP degree of protection | IP21 conforming to IEC 61800-5-1 IP21 conforming to IEC 60529 |
Degree of protection | UL type 1 conforming to UL 508C |
type of cooling | Forced convection |
Supply frequency | 50…60 Hz – 5…5 % |
Motor power kW | 90 kW (normal duty) 75 kW (heavy duty) |
Motor power hp | 125 hp normal duty 100 hp heavy duty |
Line current | 156.2 A at 380 V (normal duty) 135.8 A at 480 V (normal duty) 134.3 A at 380 V (heavy duty) 118.1 A at 480 V (heavy duty) |
Continuous output current | 173 A at 2.5 kHz for normal duty 145 A at 2.5 kHz for heavy duty |
Speed drive output frequency | 0.1…500 Hz |
Safety function | STO (safe torque off) SIL 3 |
Option card | Slot A: communication module, Profibus DP V1 Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink |
Complementary | |
Discrete input number | 8 |
Discrete input type | DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
Discrete input logic | 16 preset speeds |
Discrete output number | 0 |
Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA |
Analogue input number | 3 |
Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits AI2 voltage analog input: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
Analogue output number | 2 |
Analogue output type | Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits Software-configurable current DQ-, DQ+: 30 V DC Software-configurable current DQ-, DQ+: 100 mA |
Relay output number | 3 |
Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
Network number of phases | 3 phases |
Physical interface | Ethernet 2-wire RS 485 |
Method of access | Slave Modbus TCP |
Transmission rate | 10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Transmission frame | RTU |
Output voltage | <= power supply voltage |
Permissible temporary current boost | 1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty) |
Data format | 8 bits, configurable odd, even or no parity |
Type of polarization | No impedance |
Frequency resolution | Display unit: 0.1 Hz Analog input: 0.012/50 Hz |
Electrical connection | Control: removable screw terminals 0.5…1.5 mm²/AWG 20…AWG 16 Line side: screw terminal 120 mm²/AWG 4/0…250 kcmil Motor: screw terminal 120 mm²/250 kcmil |
Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial |
Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
Number of addresses | 1…247 for Modbus serial |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
Local signalling | 3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage |
Input compatibility | DI1…DI6: discrete input level 1 PLC conforming to IEC 61131-2 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2 |
Discrete input logic | Positive logic (source) (DI1…DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1…DI8), > 16 V (state 0), < 10 V (state 1) |
Sampling duration | 2 ms +/- 0.5 ms (DI1…DI4) – discrete input 5 ms +/- 1 ms (DI5, DI6) – discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input 10 ms +/- 1 ms (AO1) – analog output |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AO1, AO2: +/- 0.2 % for analog output |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Isolation | Between power and control terminals |
Variable speed drive application selection | Building – HVAC compressor centrifugal Food and beverage processing other application Mining mineral and metal fan Mining mineral and metal pump Oil and gas fan Water and waste water other application Building – HVAC screw compressor Food and beverage processing pump Food and beverage processing fan Food and beverage processing atomization Oil and gas electro submersible pump (ESP) Oil and gas water injection pump Oil and gas jet fuel pump Oil and gas compressor for refinery Water and waste water centrifuge pump Water and waste water positive displacement pump Water and waste water electro submersible pump (ESP) Water and waste water screw pump Water and waste water lobe compressor Water and waste water screw compressor Water and waste water compressor centrifugal Water and waste water fan Water and waste water conveyor Water and waste water mixer |
Motor power range AC-3 | 55…100 kW at 380…440 V 3 phases 55…100 kW at 480…500 V 3 phases |
Enclosure mounting | Wall mounted |
4 quadrant operation possible | False |
Asynchronous motor control profile | Constant torque standard Variable torque standard Optimized torque mode |
Synchronous motor control profile | Permanent magnet motor Synchronous reluctance motor |
Maximum output frequency | 500 kHz |
Acceleration and deceleration ramps | Linear adjustable separately from 0.01…9999 s |
Motor slip compensation | Adjustable Not available in permanent magnet motor law Automatic whatever the load Can be suppressed |
Switching frequency | 2.5…8 kHz with derating factor 2…8 kHz adjustable |
Nominal switching frequency | 2.5 kHz |
Braking to standstill | By DC injection |
Brake chopper integrated | False |
Maximum input current | 156.2 A |
Maximum output voltage | 480.0 V |
Apparent power | 112.9 kVA at 480 V (normal duty) 98.2 kVA at 480 V (heavy duty) |
Maximum transient current | 190.3 A during 60 s (normal duty) 217.5 A during 60 s (heavy duty) |
Network frequency | 50…60 Hz |
Prospective line Isc | 50 kA |
Base load current at high overload | 145.0 A |
Base load current at low overload | 173.0 A |
Power dissipation in W | Natural convection: 196 W at 380 V, switching frequency 2.5 kHz Forced convection: 1585 W at 380 V, switching frequency 2.5 kHz |
With safety function Safely Limited Speed (SLS) | False |
With safety function Safe brake management (SBC/SBT) | False |
With safety function Safe Operating Stop (SOS) | False |
With safety function Safe Position (SP) | False |
With safety function Safe programmable logic | False |
With safety function Safe Speed Monitor (SSM) | False |
With safety function Safe Stop 1 (SS1) | False |
With sft fct Safe Stop 2 (SS2) | False |
With safety function Safe torque off (STO) | True |
With safety function Safely Limited Position (SLP) | False |
With safety function Safe Direction (SDI) | False |
Protection type | Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive |
Quantity per set | 1 |
Width | 290 mm |
Height | 922 mm |
Depth | 323 mm |
Net weight | 58.5 kg |
Environment | |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Noise level | 62.4 dB conforming to 86/188/EEC |
Pollution degree | 2 conforming to IEC 61800-5-1 |
Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
Ambient air temperature for operation | -15…50 °C (without derating) 50…60 °C (with derating factor) |
Operating altitude | <= 1000 m without derating 1000…4800 m with current derating 1 % per 100 m |
Operating position | Vertical +/- 10 degree |
Product certifications | ATEX INERIS TÜV DNV-GL UL ATEX zone 2/22 CSA |
Marking | CE |
Standards | UL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 |
Maximum THDI | <48 % from 80…100 % of load conforming to IEC 61000-3-12 |
Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3 |
Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13…200 Hz |
Maximum deflection under vibratory load (during operation) | 1.5 mm at 2…13 Hz |
Permitted relative humidity (during operation) | Class 3K5 according to EN 60721-3 |
Volume of cooling air | 295 m3/h |
Overvoltage category | III |
Regulation loop | Adjustable PID regulator |
Noise level | 62.4 dB |
pollution degree | 2 |
Ambient air transport temperature | -40…70 °C |
Ambient air temperature for storage | -40…70 °C |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 47.000 cm |
Package 1 Width | 43.000 cm |
Package 1 Length | 110.000 cm |
Package 1 Weight | 66.000 kg |
Reviews