Description
SPECIFICATION
Main | |
Range | TeSys |
Product or Component Type | Contactor |
Device short name | LP1K |
Contactor application | Resistive load Motor control |
Complementary | |
Utilisation category | AC-3 AC-3e AC-1 AC-4 |
Poles description | 3P |
power pole contact composition | 3 NO |
[Ue] rated operational voltage | Power circuit <= 690 V AC <= 400 Hz Signalling circuit <= 690 V AC <= 400 Hz |
[Ie] rated operational current | 12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit 12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit 20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit |
Control circuit type | DC standard |
[Uc] control circuit voltage | 24 V DC |
Motor power kW | 3 kW 220…230 V AC 50/60 Hz AC-3 5.5 kW 380…415 V AC 50/60 Hz AC-3 5.5 kW 440 V AC 50/60 Hz AC-3 4 kW 690 V AC 50/60 Hz AC-3 3 kW 220…230 V AC 50/60 Hz AC-3e 5.5 kW 380…415 V AC 50/60 Hz AC-3e 5.5 kW 440 V AC 50/60 Hz AC-3e 4 kW 690 V AC 50/60 Hz AC-3e 3 kW 220…230 V AC 50/60 Hz AC-4 5.5 kW 380…415 V AC 50/60 Hz AC-4 5.5 kW 440 V AC 50/60 Hz AC-4 |
Auxiliary contact composition | 1 NC |
[Uimp] rated impulse withstand voltage | 8 kV |
Overvoltage category | III |
[Ith] conventional free air thermal current | 20 A (at 140 °F (60 °C)) for power circuit 10 A (at 122 °F (50 °C)) for signalling circuit |
Irms rated making capacity | 144 A AC for power circuit conforming to IEC 60947 110 A AC for signalling circuit conforming to IEC 60947 |
Rated breaking capacity | 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660…690 V conforming to IEC 60947 |
[Icw] rated short-time withstand current | 115 A 122 °F (50 °C) – 1 s for power circuit 105 A 122 °F (50 °C) – 5 s for power circuit 100 A 122 °F (50 °C) – 10 s for power circuit 75 A 122 °F (50 °C) – 30 s for power circuit 55 A 122 °F (50 °C) – 1 min for power circuit 50 A 122 °F (50 °C) – 3 min for power circuit 25 A 122 °F (50 °C) – >= 15 min for power circuit 80 A – 1 s for signalling circuit 90 A – 500 ms for signalling circuit 110 A – 100 ms for signalling circuit |
Associated fuse rating | 25 A gG at <= 440 V for power circuit 25 A aM for power circuit 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660 |
Average impedance | 3 mOhm – Ith 20 A 50 Hz for power circuit |
[Ui] rated insulation voltage | Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-5-1 Signalling circuit 600 V UL 508 Power circuit 600 V CSA C22.2 No 14 Signalling circuit 600 V CSA C22.2 No 14 |
Insulation resistance | > 10 MOhm for signalling circuit |
Inrush power in W | 3 W 68 °F (20 °C)) |
Hold-in power consumption in W | 3 W 68 °F (20 °C) |
Heat dissipation | 1.3 W |
Control circuit voltage limits | Operational: 0.8…1.15 Uc (at <122 °F (50 °C)) Drop-out: >= 0.10 Uc (at <122 °F (50 °C)) |
Connections – terminals | screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end Power circuit screw clamp terminals 2 0.002 in² (1.5 mm²)flexible with cable end |
Maximum operating rate | 3600 cyc/h |
Auxiliary contacts type | Instantaneous 1 NC |
Minimum switching current | 5 mA for signalling circuit |
Minimum switching voltage | 17 V for signalling circuit |
Mounting Support | Rail Plate |
Tightening torque | 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals pozidriv No 2 |
Operating time | 30…40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening |
Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Mechanical durability | 10 Mcycles |
Electrical durability | 1.3 Mcycles 12 A AC-3 <= 440 V 1.3 Mcycles 12 A AC-3e <= 440 V 0.3 Mcycles 20 A AC-1 <= 690 V 0.02 Mcycles 72 A AC-4 <= 440 V |
Height | 2.3 in (58 mm) |
Width | 1.8 in (45 mm) |
Depth | 2.2 in (57 mm) |
Net Weight | 0.496 lb(US) (0.225 kg) |
Environment | |
Standards | EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 |
Product Certifications | CB Scheme CCC UL CSA EAC CE UKCA |
IP degree of protection | IP2X |
Ambient air temperature for operation | -13…122 °F (-25…50 °C) |
Ambient Air Temperature for Storage | -58…176 °F (-50…80 °C) |
Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) at Uc |
Operating altitude | 6561.68 ft (2000 m) without derating |
Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
Ordering and shipping details | |
Category | US10I1222321 |
Discount Schedule | 0I12 |
GTIN | 3389110790771 |
Returnability | Yes |
Country of origin | ID |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 2.60 in (6.600 cm) |
Package 1 Width | 1.89 in (4.800 cm) |
Package 1 Length | 2.44 in (6.200 cm) |
Package 1 Weight | 7.795 oz (221.000 g) |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 40 |
Package 2 Height | 5.91 in (15.000 cm) |
Package 2 Width | 11.81 in (30.000 cm) |
Package 2 Length | 15.75 in (40.000 cm) |
Package 2 Weight | 20.327 lb(US) (9.220 kg) |
Contractual warranty | |
Warranty | 18 months |
Reviews